Parker, Max A. and Holliday, Derrick and Finney, Stephen J. (2019) DC protection for a multi-terminal HVDC network including offshore wind power, featuring a reduced DC circuit breaker count. The Journal of Engineering, 2019 (17). pp. 4511-4515. (https://doi.org/10.1049/joe.2018.8149)
Preview |
Text.
Filename: Parker_etal_JOE_2019_DC_protection_for_a_multi_terminal_HVDC_network_including.pdf
Final Published Version License: Download (3MB)| Preview |
Abstract
Large offshore wind farms located far from shore, as are being planned or built in the North Sea, will require high-voltage DC (HVDC) transmission to shore, and multi-terminal HVDC could offer further benefits. Currently proposed methods to protect against faults in the DC network are based on extremely fast-acting DC circuit breakers located on all cable ends, leading to high cost. A method is proposed based around discharging the DC network to isolate the fault, which drastically reduces the circuit breaker requirement, while making use of the inherent current-limiting behaviour of the wind turbines. The validity of this approach is demonstrated in simulation.
ORCID iDs
Parker, Max A. ORCID: https://orcid.org/0000-0001-8268-4829, Holliday, Derrick ORCID: https://orcid.org/0000-0002-6561-4535 and Finney, Stephen J. ORCID: https://orcid.org/0000-0001-5039-3533;-
-
Item type: Article ID code: 68555 Dates: DateEvent17 June 2019Published26 April 2019Published Online30 April 2018AcceptedSubjects: Technology > Electrical engineering. Electronics Nuclear engineering Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 20 Jun 2019 15:20 Last modified: 12 Dec 2024 08:13 URI: https://strathprints.strath.ac.uk/id/eprint/68555