A multi-terminal current differential protection setting method for fully weak-infeed distribution networks based on restricted enumeration method
Li, Botong and Chen, Fahui and Li, Bin and Zhang, Jing and Ji, Xiaotong and Xiao, Fan and Hong, Qiteng (2024) A multi-terminal current differential protection setting method for fully weak-infeed distribution networks based on restricted enumeration method. IEEE Transactions on Smart Grid, 15 (3). pp. 2570-2585. ISSN 1949-3061 (https://doi.org/10.1109/TSG.2023.3319484)
Preview |
Text.
Filename: Li_etal_IEEETSG_2023_A_multi_terminal_current_differential_protection_setting_method_for_fully_weak_infeed_distribution_networks.pdf
Accepted Author Manuscript License: Strathprints license 1.0 Download (2MB)| Preview |
Abstract
With the high penetration connection of inverterinterfaced distributed generators and the increasing application of large-capacity energy routers, fully weak-infeed distribution networks consisting entirely of power-electronized weak-infeed power sources are set to become one of the fundamental forms of future distribution networks. For fully weak-infeed distribution networks, multi-terminal current differential protection is considered an optional or even preferred line protection scheme. In this paper, a multi-terminal current differential protection setting method for fully weak-infeed distribution networks is proposed based on the restricted enumeration method. To address the impact of data synchronization errors and measurement errors of multi-terminal current on differential current, the problem of determining the maximum differential current superimposed with the multi-terminal current phasor errors is transformed into a high-dimensional non-convex optimization problem. The distribution law of the global optimal solution in the non-convex constraint space is deeply studied and analyzed, and a restricted enumeration method is proposed that can quickly solve the protection setting value, thereby solving the problem of multi-terminal current differential protection setting. The accuracy and rapidity of the proposed method are verified by comparing the calculation accuracy and time consumption of the restricted enumeration method and the exhaustive search. It is shown that the proposed multi-terminal differential protection setting method exhibits sufficient reliability and sensitivity in fully weak-infeed distribution networks, as verified through simulation analysis using a fully weak-infeed distribution network model built in PSCAD/EMTDC.
ORCID iDs
Li, Botong, Chen, Fahui, Li, Bin, Zhang, Jing, Ji, Xiaotong, Xiao, Fan and Hong, Qiteng ORCID: https://orcid.org/0000-0001-9122-1981;-
-
Item type: Article ID code: 86967 Dates: DateEvent1 May 2024Published30 July 2023AcceptedNotes: Copyright © 2023 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works. Subjects: Technology > Electrical engineering. Electronics Nuclear engineering > Electrical apparatus and materials > Electric networks Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 16 Oct 2023 14:23 Last modified: 16 Nov 2024 01:26 URI: https://strathprints.strath.ac.uk/id/eprint/86967