Single-loop all-pass-filter-based active damping for VSCs with LCL filters connected to the grid
Roldán-Pérez, Javier and Bueno, Emilio and Peña-Alzola, R. and Rodríguez-Cabero, Alberto; (2017) Single-loop all-pass-filter-based active damping for VSCs with LCL filters connected to the grid. In: 2017 IEEE Energy Conversion Congress and Exposition. IEEE, USA, pp. 2948-2953. ISBN 9781509029983 (https://doi.org/10.1109/ECCE.2017.8096543)
Preview |
Text.
Filename: Roldan_Perez_etal_IEEE_ECCE2017_Single_loop_all_pass_filter_based_active_damping.pdf
Accepted Author Manuscript Download (887kB)| Preview |
Abstract
LCL filters are commonly used to connect Voltage Sourced Converters (VSCs) to the grid. This type of filters are cheaper than a single inductor, but they can generate resonance problems if no active or passive damping method is used. Active damping methods are becoming popular in the literature because they improve efficiency, but they are sometimes difficult to implement and additional measurements are required. This paper proposes a method to provide active damping for VSCs connected to the grid that is based on making zero the openloop phase at the resonance frequency. It will shown that this strategy provides adequate damping of oscillations and that it can be achieved in two different ways: at the design stage (if the design constraints make it possible) or with an all-pass filter in series with the current controller. All the proposed control algorithms are verified by simulation and in a 15 kW prototype of a three-phase VSC connected to the grid with an LCL filter.
-
-
Item type: Book Section ID code: 70587 Dates: DateEvent3 November 2017Published1 May 2017AcceptedSubjects: Technology > Electrical engineering. Electronics Nuclear engineering Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 21 Nov 2019 09:02 Last modified: 18 Dec 2024 01:07 Related URLs: URI: https://strathprints.strath.ac.uk/id/eprint/70587