Centralised busbar differential and wavelet-based line protection system for multi- terminal direct current grids, with practical IEC-61869-compliant measurements

Tzelepis, Dimitrios and Dyśko, Adam and Blair, Steven M. and Rousis, Anastasios and Mirsaeidi, Sohrab and Booth, Campbell and Dong, Xinzhou (2018) Centralised busbar differential and wavelet-based line protection system for multi- terminal direct current grids, with practical IEC-61869-compliant measurements. IET Generation, Transmission and Distribution, 12 (4). pp. 3578-3586. ISSN 1751-8695 (https://doi.org/10.1049/iet-gtd.2017.1491)

[thumbnail of Tzelepis-etal-IET-GTD-2018-Centralised-busbar-differential-and-wavelet-based-line-protection-system-for-MTDC-grids]
Preview
Text. Filename: Tzelepis_etal_IET_GTD_2018_Centralised_busbar_differential_and_wavelet_based_line_protection_system_for_MTDC_grids.pdf
Accepted Author Manuscript

Download (1MB)| Preview

Abstract

This paper presents a method for discriminative detection of DC faults on VSC-powered multi-terminal HVDC transmission systems using two fundamental guiding principles, namely instantaneous current-differential and travelling waves. The proposed algorithm utilises local voltage and current measurements from all transmission lines connected to a DC busbar, and current measurement from the DC side of the converter. The scheme operates at a sampling frequency of 96 kHz which conforms with IEC 61869-9. No long distance communication is involved while measurements and signal exchange within DC substations are enabled by the utilisation of IEC 61850. Performance is assessed firstly through detailed transient simulation, using verified models of modular multi-level converters, hybrid DC circuit breakers and inductive DC-line terminations. Furthermore, practical performance and feasibility of the scheme is evaluated through laboratory testing, using the real time Opal-RT hardware prototyping platform. Simulation and experimental results demonstrate that the proposed protection algorithm can effectively, and within a very short period of time (i.e. less than 1 ms), discriminate between busbar and line faults (internal faults), while remaining stable during external faults. Additionally, it has been demonstrated that IEC 61869-9 is suitable for enabling fast DC protection schemes incorporating travelling waves.

ORCID iDs

Tzelepis, Dimitrios ORCID logoORCID: https://orcid.org/0000-0003-4263-7299, Dyśko, Adam ORCID logoORCID: https://orcid.org/0000-0002-3658-7566, Blair, Steven M. ORCID logoORCID: https://orcid.org/0000-0002-3261-4803, Rousis, Anastasios, Mirsaeidi, Sohrab, Booth, Campbell ORCID logoORCID: https://orcid.org/0000-0003-3869-4477 and Dong, Xinzhou;