Jaber, Adel A. and Lazaridis, Pavlos I. and Moradzadeh, Mohammad and Glover, Ian A. and Zaharis, Zaharias D. and Vieira, Maria F.Q. and Judd, Martin D. and Atkinson, Robert C. (2017) Calibration of free-space radiometric partial discharge measurements. IEEE Transactions on Dielectrics and Electrical Insulation, 24 (5). pp. 3004-3014. ISSN 1070-9878 (https://doi.org/10.1109/TDEI.2017.006730)
Preview |
Text.
Filename: Jaber_etal_TDEI2017_Calibration_of_free_space_radiometric_partial_discharge_measurements.pdf
Final Published Version License: Download (1MB)| Preview |
Abstract
The present study addresses the calibration of four types of partial discharge (PD) emulators used in the development of a PD Wireless Sensor Network (WSN). Three PD emulators have been constructed: a floating-electrode emulator, and two internal PD emulators. Both DC and AC high-voltage power supplies are used to initiate PD, which is measured using concurrent free-space radiometry (FSR) and a galvanic contact method based on the IEC 60270 standard. The emulators have been measured and simulated, and a good agreement has been found for the radiated fields. A new method of estimating the absolute PD activity level from radiometric measurements is proposed.
ORCID iDs
Jaber, Adel A., Lazaridis, Pavlos I., Moradzadeh, Mohammad, Glover, Ian A., Zaharis, Zaharias D., Vieira, Maria F.Q., Judd, Martin D. and Atkinson, Robert C. ORCID: https://orcid.org/0000-0002-6206-2229;-
-
Item type: Article ID code: 62665 Dates: DateEvent27 November 2017Published20 June 2017AcceptedSubjects: Technology > Electrical engineering. Electronics Nuclear engineering Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 19 Dec 2017 14:28 Last modified: 11 Nov 2024 11:49 Related URLs: URI: https://strathprints.strath.ac.uk/id/eprint/62665