Anti-short-circuit device : a new solution for short-circuiting in windcatcher and improvement of natural ventilation performance
Nejat, Payam and Calautit, John Kaiser and Majid, Muhd Zaimi Abd and Hughes, Ben Richard and Jomehzadeh, Fatemeh (2016) Anti-short-circuit device : a new solution for short-circuiting in windcatcher and improvement of natural ventilation performance. Building and Environment, 105. pp. 24-39. ISSN 0360-1323 (https://doi.org/10.1016/j.buildenv.2016.05.023)
Preview |
Text.
Filename: Nejat_etal_BE_2016_Anti_short_circuit_device_a_new_solution_for_short_circuiting_in_windcatcher.pdf
Accepted Author Manuscript License: Download (1MB)| Preview |
Abstract
Windcatcher is an effective technique for naturally ventilating a space and improving indoor air quality. A common problem for modern and traditional windcatchers is air short-circuiting. Air-short-circuiting in windcatchers occurs when the air entering through the supply channel immediately exits through the exhaust channel without circulating and mixing inside the enclosed space. Several previous works on windcatchers have observed the "short-circuiting" effect and concluded that it has a negative impact on the ventilation performance however, no work have provided a solution to eliminate this effect. The present study will address this issue by incorporating a component called the anti-short-circuiting device (ASCD) and investigating its potential to eliminate air short-circuiting in windcatchers and improve ventilation performance. Two methods were employed in this research: experimental and Computational Fluid Dynamics (CFD) study. For the experimental work, three scaled models were studied in a wind tunnel. The CFD modelling was validated using the air velocity measurements and good correlation was observed with average error below 10%. The results showed that the ASCD windcatcher with angles between 20° and 80° prevented air-short-circuiting while supplying up to 40-51 l/s per occupant, which is higher than the minimum recommendations of ASHRAE62.2 and BS5925. In addition, the windcatcher without ASCD showed 8% higher CO2 concentration in the room, indicating that the ASCD windcatcher was more effective in removing stale air out of the room. Furthermore, the average air velocity in the room at sitting height with the ASCD windcatcher was 19-28% higher than windcatcher without ASCD.
-
-
Item type: Article ID code: 73401 Dates: DateEvent15 August 2016Published20 May 2016Published Online17 May 2016AcceptedSubjects: Technology > Mechanical engineering and machinery
Technology > Building constructionDepartment: Faculty of Engineering > Mechanical and Aerospace Engineering Depositing user: Pure Administrator Date deposited: 30 Jul 2020 14:09 Last modified: 12 Dec 2024 09:55 Related URLs: URI: https://strathprints.strath.ac.uk/id/eprint/73401