Research at CSHHH explores the modern world since 1800 in locations as diverse as the UK, Asia, Africa, North America, and Europe. Areas of specialism include contraception and sexuality; family health and medical services; occupational health and medicine; disability; the history of psychiatry; conflict and warfare; and, drugs, pharmaceuticals and intoxicants.

Explore the Open Access research of the Centre for the Social History of Health and Healthcare. Or explore all of Strathclyde's Open Access research...

Image: Heart of England NHS Foundation Trust. Wellcome Collection - CC-BY.

Improved protection system for phase faults on marine vessels based on ratio between negative-sequence and positive-sequence of the fault current

Ciontea, Catalin and Hong, Qiteng and Booth, Campbell and Bak, Claus and Blaabjerg, Frede and Madsen, Kjeld and Sterregaard, Claes (2018) Improved protection system for phase faults on marine vessels based on ratio between negative-sequence and positive-sequence of the fault current. IET Electrical Systems in Transportation. ISSN 2042-9738

[img]
Preview
Text (Ciontea-etal-IET-EST-2018-Improved-protection-system-for-phase-faults-on-marine-vessels)
Ciontea_etal_IET_EST_2018_Improved_protection_system_for_phase_faults_on_marine_vessels.pdf
Accepted Author Manuscript

Download (1MB) | Preview

Abstract

This paper presents a new method to protect the radial feeders on marine vessels. The proposed protection method is effective against Phase-Phase (PP) faults and is based on evaluation of the ratio between the negative-sequence and positive-sequence of the fault currents. It is shown that the magnitude of the introduced ratio increases significantly during the PP fault, hence indicating the fault presence in an electric network. In this paper, the theoretical background of the new method of protection is firstly discussed, based on which the new protection algorithm is described afterwards. The proposed algorithm is implemented in a programmable digital relay embedded in a Hardware-in-the-Loop (HIL) test setup that emulates a typical maritime feeder using a Real Time Digital Simulator (RTDS). The HIL setup allows testing of the new protection method under a wide range of faults and network conditions and the experimental results demonstrate its effectiveness in all scenarios conducted. The proposed protection method offers a solution to the protection challenges associated with variability of the short-circuit currents in radial feeders, advancing in this way the traditional mean of protection in maritime feeders, represented by OverCurrent (OC) relays.