Performance of loss-of-mains detection in multi-generator power islands
Tzelepis, Dimitrios and Dysko, Adam and Booth, Campbell (2016) Performance of loss-of-mains detection in multi-generator power islands. In: The 13th IET International Conference on Developments in Power System Protection 2016, 2016-03-07 - 2016-03-10, The Sheraton Hotel.
Preview |
Text.
Filename: Tzelepis_etal_DPSP_2016_loss_of_mains_detection_in_multi_generator_power_islands.pdf
Accepted Author Manuscript Download (1MB)| Preview |
Abstract
This paper presents an investigation of the impact of multi-generator power islands on the performance of the most-commonly used anti-islanding protection method, Rate of Change of Frequency (ROCOF). In particular, various generating technology mixes including Photovoltaic panels (PV), Doubly Fed Induction Generators (DFIGs) and Synchronous Generators (SG) are considered. The Non-Detection Zone (NDZ) for a range of ROCOF setting options is assessed systematically and expressed as a percentage of generator MVA rating. It was discovered that ROCOF protection becomes very ineffective when protection time delay is applied. In the majority of islanding situations the generator is disconnected by frequency-based G59 protection.
ORCID iDs
Tzelepis, Dimitrios ORCID: https://orcid.org/0000-0003-4263-7299, Dysko, Adam ORCID: https://orcid.org/0000-0002-3658-7566 and Booth, Campbell ORCID: https://orcid.org/0000-0003-3869-4477;-
-
Item type: Conference or Workshop Item(Paper) ID code: 55387 Dates: DateEvent10 March 2016Published8 January 2016AcceptedSubjects: Technology > Electrical engineering. Electronics Nuclear engineering Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 28 Jan 2016 11:19 Last modified: 11 Nov 2024 16:46 Related URLs: URI: https://strathprints.strath.ac.uk/id/eprint/55387