Source-independent Zone-1 protection for converter-dominated power networks

Paladhi, Subhadeep and Kurre, Jaisaikiran Reddy and Pradhan, Ashok Kumar (2024) Source-independent Zone-1 protection for converter-dominated power networks. IEEE Transactions on Power Delivery, 39 (1). pp. 341-351. ISSN 0885-8977 (https://doi.org/10.1109/TPWRD.2022.3218615)

[thumbnail of Paladhi-etal-TPD-2022-Souce-independent-zone-1-protection-for-converter-dominated-power-networks]
Preview
Text. Filename: Paladhi_etal_TPD_2022_Souce_independent_zone_1_protection_for_converter_dominated_power_networks.pdf
Accepted Author Manuscript
License: Strathprints license 1.0

Download (1MB)| Preview

Abstract

Growing penetration of converter-interfaced renewable energy sources with numerous control operations results in non-homogeneous fault characteristics in the network. Distance relay Zone-1 operation with such non-homogeneous situation may be vulnerable compromising both dependability and security aspects. In this work, vulnerability analysis is carried out to identify the factors influencing Zone-1 performance in a renewable integrated power network, and a method is proposed to ensure its correct operation. The method considers the homogeneity present in negative and zero sequence networks with converter-based sources to obtain the faulted loop current angle using local measurements and to derive correct decisions. The proposed method is tested for different renewable integrated systems, even with 100% converter-based sources and with variations in different vulnerable factors. Comparison with available distance relaying techniques demonstrates the superior performance of the proposed method.