Adaptive zone-1 setting following structural and operational changes in power system
Paladhi, Subhadeep and Pradhan, Ashok Kumar (2018) Adaptive zone-1 setting following structural and operational changes in power system. IEEE Transactions on Power Delivery, 33 (2). pp. 560-569. ISSN 0885-8977 (https://doi.org/10.1109/TPWRD.2017.2728682)
Preview |
Text.
Filename: Paladhi_Pradhan_IEEE_TOPD_2017_Adaptive_zone_1_setting_following_structural_and_operational_changes.pdf
Accepted Author Manuscript Download (2MB)| Preview |
Abstract
Change in the network structure or operating condition in a power system affects the impedance as calculated by the distance relay during fault. Such changes may lead to malfunction of the distance relay at times. In this paper, an adaptive distance relay setting method using local data is proposed to prevent zone-1 malfunction following structural and operational changes. The performance of the proposed adaptive setting method is tested on a 39-bus New England system and a generic 12-bus power system using PSCAD/EMTDC simulation data, and a comparative assessment is also provided.
ORCID iDs
Paladhi, Subhadeep ORCID: https://orcid.org/0000-0001-8649-7713 and Pradhan, Ashok Kumar;-
-
Item type: Article ID code: 76162 Dates: DateEvent30 April 2018Published18 July 2017Published Online12 July 2017AcceptedNotes: © 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting /republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works. Subjects: Technology > Electrical engineering. Electronics Nuclear engineering Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 20 Apr 2021 09:32 Last modified: 12 Dec 2024 11:13 URI: https://strathprints.strath.ac.uk/id/eprint/76162