Assessing the impact of DFIG synthetic inertia provision on power system small-signal stability
Lucas, Edgar and Campos-Gaona, David and Anaya-Lara, Olimpo (2019) Assessing the impact of DFIG synthetic inertia provision on power system small-signal stability. Energies, 12 (18). 3440. ISSN 1996-1073 (https://doi.org/10.3390/en12183440)
Preview |
Text.
Filename: Lucas_etal_Energies_2019_Assessing_the_impact_of_DFIG_synthetic_inertia.pdf
Final Published Version License: Download (448kB)| Preview |
Abstract
Synthetic inertia provision through the control of doubly-fed induction generator (DFIG) wind turbines is an effective means of providing frequency support to the wider electrical network. There are numerous control topologies to achieve this, many of which work by making modifications to the DFIG power controller and introducing additional loops to relate active power to electrical frequency. How these many controller designs compare to one-another in terms of their contribution to frequency response is a much studied topic, but perhaps less studied is their effect on the small-signal stability of the system. The concept of small-signal stability in the context of a power system is the ability to maintain synchronism when subjected to small disturbances, such as those associated with a change in load or a loss of generation. Amendments made to the control system of a large-scale wind farm will inevitably have an effect on the system as a whole, and by making a DFIG wind turbine behave more like a synchronous generator, which synthetic inertia provision does, may incur consequences relating to electromechanical oscillations between generating units. This work compares the implications of two prominent synthetic inertia controllers of varying complexity and their effect on small-signal stability. Eigenvalue analysis is conducted to highlight the key information relating to electromechanical modes between generators for the two control strategies, with a focus on how these affect the damping ratios. It is shown that as the synthetic inertia controller becomes both more complex and more effective, the damping ratio of the electromechanical modes is reduced, signifying a decreased system stability.
ORCID iDs
Lucas, Edgar, Campos-Gaona, David ORCID: https://orcid.org/0000-0002-0347-6288 and Anaya-Lara, Olimpo ORCID: https://orcid.org/0000-0001-5250-5877;-
-
Item type: Article ID code: 69893 Dates: DateEvent6 September 2019Published4 September 2019AcceptedSubjects: Technology > Electrical engineering. Electronics Nuclear engineering Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 20 Sep 2019 14:39 Last modified: 04 Dec 2024 01:21 Related URLs: URI: https://strathprints.strath.ac.uk/id/eprint/69893