Partial discharge location using unsynchronized radiometer network for condition monitoring in HV substations – a proposed approach
, ed. (2012) Partial discharge location using unsynchronized radiometer network for condition monitoring in HV substations – a proposed approach. Journal of Physics Conference Series, 364 (1). 012053. ISSN 1742-6588 (https://doi.org/10.1088/1742-6596/364/1/012053)
Full text not available in this repository.Request a copyAbstract
A location estimation system for online Partial Discharge (PD) detection is proposed as a low-cost approach to real-time condition monitoring, asset management and operation optimization in future smart grid. Some early progress in the development of subsystems (specifically the antenna, radiometer device, PD emulator and PD generator) for a proof-of-principle prototype system is described. The proposed PD Wireless Sensor Network (WSN) uses a novel approach to PD location which obviates the need for synchronization between sensors thereby improving scalability.
-
-
Item type: Article ID code: 40304 Dates: DateEvent2012PublishedSubjects: Technology > Electrical engineering. Electronics Nuclear engineering Department: Faculty of Engineering > Electronic and Electrical Engineering Depositing user: Pure Administrator Date deposited: 02 Jul 2012 13:47 Last modified: 08 Apr 2024 20:00 Related URLs: URI: https://strathprints.strath.ac.uk/id/eprint/40304