Moore, P.J. and Al-Nasseri, H. (2004) Improved zone 2 acceleration scheme using sound phase seen impedance. In: Eighth IEE International Conference on Developments in Power System Protection 2004, 2004-04-05 - 2004-04-08, Amsterdam.
Full text not available in this repository. (Request a copy from the Strathclyde author)Official URL: http://dx.doi.org/10.1049/cp:20040160
Abstract
The acceleration of distance protection zone 2 schemes usually relies on the use of a communications channel. This paper describes a scheme capable of detecting the operation of the remote-end circuit breaker by analysing the seen impedance on sound phase elements in the relay. A series of simulation studies have shown that the technique works under a variety of system conditions. It proposed that the technique is used as a backup when the communications channel is unavailable.
| Item type: | Conference or Workshop Item (Paper) |
|---|---|
| ID code: | 38240 |
| Keywords: | power transmission faults , relay protection , power transmission protection, improved zone, acceleration scheme, sound phase, seen impedance , Electrical engineering. Electronics Nuclear engineering |
| Subjects: | Technology > Electrical engineering. Electronics Nuclear engineering |
| Department: | Faculty of Engineering > Electronic and Electrical Engineering |